PowerShield Centurion RT 1000VA Long Run Online UPS. No

$1,198.36 incl gst

POWERSHIELD Centurion RT 1000VA Long Run Online UPS. No Internal Batteries, PSRTBB6 or External battery bank must be used. 8A Internal Charger.

Out of stock

SKU: PSCERT1000L Category:

Description

 

POWERSHIELD Centurion RT 1000VA Long Run Online UPS. No Internal Batteries, PSRTBB6 or External battery bank must be used. 8A Internal Charger.

As a true online double conversion UPS the Centurion RT is our highest single phase power density UPS. Boasting an output power factor of 0.9, this will fully protect mission-critical devices as it can support larger loads than UPS products of an equal VA rating.

The Centurion RT has an energy saving Advanced ECO mode, which allows the unit to operate at very high efficiency, up to 98%. When the utility mains input voltage is within the ECO range the UPS saves energy by passing the mains supply directly through to the load, while the inverter continues to operate in a passive mode.

 

Features:

  • True double-conversion
  • Output power factor 0.9
  • User-friendly and electronic easy-shift LCD display
  • Rack or Tower design
  • Advanced ECO mode for energy saving
  • Generator compatible
  • Programmable power management outlets
  • Emergency Power Off function (EPO)
  • Hot-swappable battery design
  • Ideal for medium density power protection
  • Extra large charger

 

 PSCERT1000L RT BATTERY BANKS: PSRTBB12
Capacity 1000VA/900W
Topology True online double- conversion, Pure Sine Wave
INPUT
Voltage Range Low Line Transfer 160V/140V/120V/110V AC ±5% (based on load percentage 100%-80%/80%-70%/70%-60%/60%-0)
Low Line Comeback 175V/155V/135V/25V AC ±5%
High Line Transfer 300V AC ±5%
High Line Comeback 290V AC ±5%
Frequency Range 40Hz ~ 70Hz
Phase Single phase with ground
Power Factor Correction  ≥0.99 @ nominal voltage (100% load)
OUTPUT
Output Power Factor 0.9
Output Voltage (AC Mode) 240V AC (Selectable 200/208/220/230/240V AC)
Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Batt. Mode) 50Hz or 60Hz ±1Hz
Current Crest Ratio 3:1 (max.)
Transfer AC Mode to Batt. Mode 4ms (Typical)
Inverter to Bypass Pure Sine Wave
EFFICIENCY
ECO Mode (Advanced) 96%
Battery Mode 86%
BATTERY
Battery Number (12Vx9AH) x 3
Typical Recharge Time 4 hours recover to 90% capacity (for the standard model only)
Charging Current (max.) Standard Models – 1.5Amp. Long Run Models – 1Amp/2Amp/4Amp/6Amp selectable (factory default is 6Amp)
PROTECTION
Full Protection Overload, discharge, thermal, short circuit and overcharge protection
Surge Protection 984 Joules/22000A
COMMUNICATIONS AND MANAGEMENT
Interface USB or RS232 as standard, Intelligent slot for PSSNMP, PSModbus or PSAS400 dry contact
Software PowerShield® NetGuard® software – supports Windows-based operating systems, Linux, Unix and Mac
LCD Display/Alarm UPS Status, Load & Battery Level, Input/Output Voltage, Batt. Time Remaining and Fault Indicators
Audible Alarm Battery Mode, Bypass Mode, Low Battery (Batt. Mode), Fault, Overload
PHYSICAL
Dimension, (D x W x H) 380 x 438 x 88mm 480 x 438 x 88mm
Weight 8.4kg 22kg
OPERATING ENVIRONMENT
Temperature 0°C ~ 40°C
Humidity 20% ~ 90% (RH Non-condensing)
COMPLIANCE
Safety/EMC/RoHS EN62040-1-1 2003, IEC60950-1-1/EN62040-2 2006/Directive 2011/65/EU

 

 