PowerShield Centurion RT 1000VA/ 900W Double Conversion True

$1,206.36 incl gst

POWERSHIELD Centurion RT 1000VA/ 900W Double Conversion True Online UPS. Power Factor 0.9 Rack/Tower Design (2RU) Hot-Swappable Battery. EBM Compatible to Extend Runtime.

Out of stock

SKU: PSCERT1000 Category:

Description

 

POWERSHIELD Centurion RT 1000VA/ 900W Double Conversion True Online UPS. Power Factor 0.9 Rack/Tower Design (2RU) Hot-Swappable Battery. EBM Compatible to Extend Runtime.

The Centurion RT has an energy saving Advanced ECO mode, which allows the unit to operate at very high efficiency, up to 98%. When the utility mains input voltage is within the ECO range the UPS saves energy by passing the mains supply directly through to the load, while the inverter continues to operate in a passive mode.

The Centurion RT incorporates hot-swappable internal battery packs which can be accessed via the front panel for maintenance changes, keeping the UPS operational during battery replacement. Battery backup time can be increased by simply adding additional Battery Banks. The standard Centurion RT has been designed with a larger charger than others ensuring rapid recharge times when adding additional battery banks.

The LCD display panel is readily viewable whether the UPS is horizontal or vertical. The display Menu is simple and intuitive. It displays all critical and noncritical parameters, including the estimated battery backup time remaining. This UPS comes with programmable power management outlets allowing the user to control load segments, thereby extending battery backup times to mission-critical devices by shutting down noncritical items.

The Centurion RT has been meticulously developed by Power Shield engineers to address absolutely all requirements and features as has been demanded by the sophisticated Australian power consumer and hence the Centurion RT stands in a class of its own, as a world-leading UPS technology.

 

Features

  • Surge Protection Best in its Class – 984J/22000A
  • True online double-conversion
  • Power factor 0.9
  • Extra large charger for rapid recharging
  • Option to add additional battery banks to increase backup time
  • User-friendly, electronic easy-shift LCD display
  • Rack or Tower design
  • Advanced ECO mode for energy saving
  • Generator compatible
  • Programmable power management outlets
  • EPO – Emergency Power Off function
  • Hot-swappable battery design
  • USB, RS232, SNMP, Modbus, Environmental Monitoring and AS400 multiple communications available

 

INPUT  

Voltage Range Low Line Transfer 160Vac / 140Vac / 120Vac / 110Vac ± 5%
(based on load percentage 100% – 80% /
80% – 70% / 70% – 60% / 60% – 0)
Low Line Comeback 170Vac / 150Vac / 130Vac / 120Vac ± 5%
High Line Transfer 300Vac ± 5%
High Line Comeback 290Vac ± 5%
Frequency Range 40Hz – 70Hz
Phase Single phase with ground
Power Factor Correction >0.99 @ nominal voltage (100% load)

OUTPUT

Output Power Factor: 0.9
Output Voltage (AC Mode) 240Vac (Selectable 208/220/230/240Vac)
Voltage Regulation (Bat. Mode) ±1%
Frequency Range (Batt. Mode) 50Hz or 60Hz ±1Hz
Current Crest Ratio 5:1 (max.)
Transfer Time 4ms (Typical)

EFFICIENCY 

ECO Mode (Advanced) 98%
Battery Mode 86%

BATTERY 

Battery Type & Number 12 V*9AH (x3)
Typical Recharge Time 4 hours recover to 90% capacity
Charging Current (max.) Standard Model -1.5Amp, Long Run Model –
1Amp/2Amp /4Amp/6Amp (factory default is 6Amp)

PROTECTION 

Full Protection Overload, discharge, thermal,
short circuit and overcharge protection
Surge Protection 984 Joules / 22000 Amps

COMMUNICATIONS & MANAGEMENT 

Interface USB or RS232 as standard, Intelligent slot
for PSSNMP, PSModbus or PSAS400 dry contact
Software PowerShield NetGuard® software –
supports Windows based operating systems,
Linux, Unix and Mac
LCD Display/Alarm UPS Status, Load & Battery Level,
Input/Output Voltage, Batt. Time
Remaining and Fault Indicators
Audible Alarm Battery Mode, Bypass Mode, Low Battery (Batt. Mode),
Fault, Overload

PHYSICAL

Dimension (D x W x H) 480 x 438 x 88 mm
Weight 18kg

OPERATING ENVIRONMENT 

Temperature 0 – 40°C
Humidity 20 – 90% (RH Non-condensing)
Noise Level < 50dBA @ 1 Meter

COMPLIANCE 

Safety EN62040-1-1 2003, IEC60950-1-1
EMC EN62040-2 2006
RoHS Directive 2011/65/EU

 

 

Brand

powershield

Reviews

There are no reviews yet.

Be the first to review “PowerShield Centurion RT 1000VA/ 900W Double Conversion True”